|
Designers and Installers make costly grounding mistakes by not following
grounding requirements for more than one building or structure supplied from a
common service.
A change in the l990 NEC© keeps catching designers and installers. The
change applies to the grounding requirements where two or more buildings or
structures are supplied by a common service, and where the disconnecting means
is located in a separate building or Structure. Normally a disconnecting means
is required to be located at each building or structure, but the 1993 NEC©
Section 225-8(b) Exception No. l gives permission for the disconnecting means
to be located elsewhere on the premises other than at a building or structure
for large capacity multibuilding industrial installations under single
management, and where it is assured that disconnecting can be accomplished by
establishing and maintaining "safe switching procedures." This
exception is often used where hazardous locations are encountered so that the
disconnecting means can be located in a nonhazardous area. When this design is
used, NEC© Section 250-24(c) that was added to the 1990 NEC© must be
complied with by bonding the grounding conductor at each separate building or
structure to a grounding electrode. The 1990 NEC© required that this
bonding be done at a junction box located immediately inside or outside of the
separate building or structure. The 1993 NEC© elaborates on this by
allowing the bonding to take place in a junction box, panelboard, or similar
enclosure located immediately inside or outside the separate building or
structure. The purpose of this bonding is to shunt lightning discharges to the
earth at the separate building or structure. There are some practical
limitations that should be applied. For instance, these requirements may not
apply to a lighting pole or to a unistrut frame used at a lift station. However,
these requirements would surely apply to a truck loading facility, a tank farm,
or a process facility found at refineries.
|