Example 2 from NEC Handbook Section 220.40
Given:
Feeder Circuit with following parameters.
3 phase 4 wire feeder full size
Neutral 125 ampere noncontinuous load 200 ampere continuous load 75
Degree C terminal temperature rating Type THHN insulated conductors (THWN
was given in the original problem, but was changed to THHN in the solution)
Four current carrying copper conductors in a raceway Majority of load is
nonlinear Solution : 600 kcmil conductors
protected by a 400 ampere overcurrent protective device (OCPD)
Example 3 from NEC Handbook Section 210.20(A)
Given:
Branch Circuit with following parameters.
25 ampere continuous load 60
Degree C terminal temperature rating Type THWN insulated conductors
Four current carrying copper conductors in a raceway Majority of load is
nonlinear Solution: No. 8 AWG conductors
protected by a 35 ampere overcurrent protective device (OCPD)
Example 4 from Mike Holt online examples
Given:
Branch Circuit with following parameters.
53 ampere continuous load 75
Degree C terminal temperature rating Type THHN insulated conductors
Four current carrying copper conductors in a raceway Majority of load is
nonlinear Solution : No. 4 AWG conductors
protected by a 70 ampere overcurrent protective device (OCPD)
Example 5 from Mike Holt online Examples
Given:
Feeder Circuit with following parameters.
3 phase 4 wire feeder full size
Neutral 184 ampere continuous load 75
Degree C terminal temperature rating Type THHN insulated conductors
Four current carrying copper conductors in a raceway Solution: 250 kcmil conductors
protected by a 250 ampere overcurrent protective device (OCPD)
Example 6 from McGraw-Hill's NEC
Handbook
Given:
Branch Circuit with following parameters.
100 ampere continuous load 75
Degree C terminal temperature rating Type THHN and THW insulated conductors
Four current carrying copper conductors in a raceway Majority of load is
nonlinear Solution :
No. 1 AWG THHN or No. 1/0 AWG THW conductors
protected by a 125 ampere overcurrent protective device (OCPD)
In this example the
minimum feeder-circuit conductor size, before the application of any
adjustment or correction factors, shall have an allowable ampacity not less
than the noncontinuous load plus 125 percent of the continuous load.
Therefore, we take 125 percent of the load, 100 amperes, to get 125 amperes.
We next go to the 90 degree column for THHN and select No. 1 AWG that has an
ampacity of 150 amperes. Next we apply the derating factor of 0.8.
0.8 x 150 = 120 amperes. This is sufficient to carry the 100 ampere
continuous load per the rule. We next select the next higher OCPD at
125 amperes. If we had selected
No. 2 at 130 amperes then multiplied by 0.8 we would get 104 amperes.
Then the next higher OCPD would be 110 amperes which is not sufficient.
The OCPD must also be sized for the continuous load which in this case
requires a OCPD of 125 amperes minimum.
Ref: 210.20(A)
(A) Continuous and Noncontinuous Loads. Where a branch circuit supplies
continuous loads or any combination of continuous and noncontinuous loads,
the rating of the overcurrent device shall not be less than the
noncontinuous load plus 125 percent of the continuous load.
215.3 Where a feeder supplies continuous loads or any
combination of continuous and noncontinuous loads, the rating of the
overcurrent device shall not be less than the noncontinuous load plus 125
percent of the continuous load.
Example 7 Nonmetallic Cable
Given:
Branch Circuit with following parameters.
16 ampere continuous load Four each 2-conductor w/ground NM cables in a 36 inch long raceway used for firestopping.
Conductors are copper Analysis:
Per Section 334.80
The ampacity of Types NM, NMC, and NMS
cable shall be determined in accordance with 310.15.
The ampacity shall be in
accordance with the 60°C conductor temperature rating. The 90°C
rating shall be permitted to be used for ampacity derating purposes,
provided the final derated ampacity does not exceed that for a 60°C rated
conductor. To apply these
rules select the conductor as "NM Cable - 90 C" and the terminal temperature
as "NM - 60 C." There are 8 current carrying conductors.
Solution : No.
12 conductors
protected by a 20 ampere overcurrent protective device (OCPD)
|