Table 348.22 Maximum Number of Insulated Conductors in 3/8 inch
Flexible Metal Conduit and Liquidtight Flexible Metal Conduit*
Types RFH-2, SF-2
Types TF, XHHW,
AF, TW
Types TFN, THHN,
THWN
Types FEP, FEPB,
PF, PGF
Size
(AWG)
Fittings
Inside
Conduit
Fittings
Outside
Conduit
Fittings
Inside
Conduit
Fittings
Outside
Conduit
Fittings
Inside
Conduit
Fittings
Outside
Conduit
Fittings
Inside
Conduit
Fittings
Outside
Conduit
18
2 3 3 5 5 8 5 8
16
1 2 3 4 4 6 4 6
14
1 2 2 3 3 4 3 4
12
- - 1 2 2 3 2 3
10
- - 1 1 1 1 1 2
* In addition, one covered or bare equipment grounding conductor of the same size shall be permitted.