Bar
.
Articles
Bar


Transformers Not Properly Grounded

  The common 30, 45, 75, 112.5, and 150 KVA 480/208/120 Volt, Delta to Y Dry-type transformers are being found without grounding electrode conductors and without a grounding electrode as required by the NEC section 250-26. These transformers of the solidly-grounded type are "separately derived AC systems," and the grounding requirements are almost like a service. The grounded conductor terminal, commonly referred to as XO, on the secondary side must be grounded to the nearest available effectively grounded structural member (building steel), water pipe, or other electrodes as specified in NEC section 250-81 and 250-83 where the effectively grounded structural member (building steel) or water pipe are not available. "The grounding electrode shall be as near as practical to and preferably in the same area as the grounding conductor connection to the system." This system is not the service system but the separately derived A.C. system.

Also, a bonding jumper sized in accordance to 250-79(d) for the derived phase conductors must bond the grounded conductor to the equipment grounding conductors.

Engineers and installers repeatedly attempt to use the equipment grounding conductor brought in with the primary power as a grounding electrode conductor. This is a clear violation of NEC section 250-26.


© 1996 Gerald Newton. All rights reserved.
 
---