|
|
Wet Locations
If we had to install conductors in a wet location most of us would
immediately know to use a type W conductor such as XHHW, THW or THWN. But just
what is a wet location? The answer to this can be found in Article 100 under
the definition of "Location." Raceways installed in concrete slabs,
out-of-doors where exposed to the weather, and installations underground are
examples of wet Locations. But what about the inside of the conduit? Is this a
wet location? To answer this, we must go to the NFPA NEC Handbook and read the
explanatory material. There it states that the intent is that the inside of a
raceway located in a wet location is also a wet location. Easy enough, right?
But we all know that the explanatory material is not mandatory, regardless of
being found in the NFPA Handbook. However, most of us would agree with these
explanations. So what is the problem? The problem arises when instrument
cables, for instance, Class 2 cables, are installed in conduits located in wet
locations. According to U.L., there arent any Class 2 cables listed for
use in a wet location without also being listed for direct burial. Some will
argue, what is the hazard? If I want to install Class 2 cables in wet locations,
there is no shock hazard, no ignition hazard, and if the cables are properly
listed, no spread of fire hazard. This is true. But there may be other hazards
if the cables are used to control an integrated electrical system requiring an
orderly shutdown where failure of the cables may result in an oil spill. This
is a hazard not normally considered, but may be considered by other authorities
such as the Alaska Department of Environmental Conservation. Therefore, the
Class 2 cables installed in a wet location may have to be listed for wet
locations.
Hazardous Location
If these cables are also installed in a Class 1 Division 2 hazardous
location NEC section 725-53(d) requires that the cables be Power Limited Tray
Cable (PLTC). However, the only PLTC cables listed for wet locations are the
Direct Burial type. An exception to NEC section 725-53(d) allows other types of
cables if the circuits are intrinsically safe. We could install Class 2 cables
on Class 2 intrinsically safe circuits in a Class 2, Division 2 hazardous
location, but, again, if the location is also a wet location the cables may
have to be listed for wet locations. Note, we said if the cables are Class 2 and
intrinsically safe: Remember, intrinsically safe circuits are not necessarily
Class 2 circuits. If the cables are also installed in a cable tray NEC section
725-53(c) states that they must be type PLTC unless the cables are for
thermocouple circuits. Therefore, for a location that is wet and Class 2,
Division 2, cables in cable tray would have to be PLTC suitable for direct
burial since these are the only PLTC cables listed for wet locations.
Other Space used for Environmental Air
If this scenario is expanded to cover other space used for environmental
air the cable tray is required by NEC section 300-22(c) to have a solid bottom
with a solid cover, or else the cables must be Plenum rated, type Ml, type AC,
or type MC without an overall nonmetallic covering. If the cables are plenum
rated and not PLTC they cannot be installed in a cable tray by NEC section
725-53(c). Suppliers have had difficulty finding PLTC cables that are plenum
rated. When designing these types of installations it is recommended that the
authority having jurisdiction be contacted and requested to perform a plan
review.
|