Overview
Probably one of the more confusing tasks in using the 1996 (and now the 1999) NEC is
applying Table 310-16, accompanying notes, and code sections. There have been
several articles written on this, and new code books and video tapes have tried
to address the issue. I have reviewed these and more and found using Table
310-16 to be a complex task. I finally wrote an excel spreadsheet computer program
to make the task easier for all of us .
The selection of the correct conductor size and overcurrent protection
requires four independent processes for selecting four independent overcurrent
devices (OCPD's), then the four overcurrent devices must be tested to find which
set is correct, and if they do not pass the test then the next higher conductor
size must be selected and three of the processes must be repeated until the four
independently selected OCPD's pass the test. The correct conductor size is a
by-product of this overall process.
Find the the Low Load and Select the Low Load OCPD
This load is going to be called the Low Load. So keep in mind that
throughout this article the low load is the Low Load and the units is amperes.
The definition of this load varies. If the final selected OCPD is listed for
use at its rating at 100 per cent continuous load the Low Load is the sum of the
Noncontinuous load and the Continuous load. If the OCPD is not listed for use
at 100 per cent of its rating for a continuous load then the Low Load is equal
to the sum of the noncontinuous load and 125 per cent of the continuous load. A
continuous load is defined in the NEC as a load that continues for three hours
or more. The Low Load is used to select the OCPD from Section 240-6. The OCPD
that is equal to the Low Load or the next Higher OCPD is selected. This OCPD is
call the Low Load OCPD.
Find the Conductor Size and the maximum OCPD-1 for this Conductor
This is the more complex of the four processes. The conductor size is
required before we can perform the fourth process, selecting the Maximum OCPD
for the terminal temperature.
First we must find another load current. In this case we will call this
Load our Conductor Load Current that may be equal to or less than the Low Load
current that we found previously. The Conductor Load Current is equal to the
sum of the noncontinuous load plus the continuous load. Next we use the
Conductor Load Current to select the wire size from Table 310-16.
To select the correct conductor size we must know the insulation
temperature and the total derating factor. The total derating factor is the
product of the ambient derating factor from the bottom of Table 310-16 and the
derating factor from Note 8 to table 310-16, the derating factor for over three
current carrying conductors in a raceway, cable, or trench. The Note 8 derating
factor is one for up to three current carrying conductors in the same raceway,
cable, or trench. Likewise, the derating factor for an ambient temperature of
26 to 30 degrees C. is one. We must multiply the ampacities in Table 310-16 for
the type of conductor insulation by the total derating factor and find the
conductor size that has a derated ampacity at or above the Conductor Load
Current.
There is more to this than meets the eye. Since we can have a conductor
with a 60, 75, or 90 degree C. insulation terminated on a 60, 75 or 90 degree
C. termination there are nine ampacity tables instead of three. When a higher
temperature conductor insulation is used on a lower temperature conductor
termination, the conductor size is selected by choosing the the size of
conductor having the lower temperature ampacity that is greater than or equal to
the conductor load current and having its own higher temperature ampacity
multiplied by the total derating factor greater than or equal to the conductor
load current. When a conductor is used at its insulation temperature on a
termination at or above its insulation temperature the same selection process is
used, but only the conductor's ampacity at its rated insulation temperature
multiplied by the total derating factor is checked against the conductor load
current to make sure that the conductor selected has a derated ampacity greater
than or equal to the conductor load current.
Next we must find the OCPD for this conductor size. The OCPD selection
is done using the derated ampacity for the size and temperature of the conductor
that was selected above. We multiply the total derating factor times the Table
310-16 ampacity for the conductor selected above to find the conductor derated
ampacity. The selection of this OCPD depends on one other variable, whether or
not the circuit is a branch circuit supplying multiple receptacles and outlets.
If the circuit is of this type then the OCPD is selected using section 240-6 so
that the OCPD is equal to or is the next lower OCPD below the derated conductor
ampacity. Otherwise, the OCPD is selected such that it is equal to or is the
next higher OCPD above the derated conductor ampacity using section 240-6. The
OCPD selected in this process is called OCPD-1.
Find OCPD-2 for Table 310-16 oblisks and Table 210-24 conditions
There are some other conditions that apply to the OCPD. Table 310-16 has
several obelisks notes at the bottom. If the wire size selected above is No. 14
copper then the OCPD must not exceed 15 amperes, and for No. 12, 20 amperes, and
for No. 10, 30 amperes. Also if the circuit is for multiple outlets or
receptacles Table 210-24 limits the OCPD to 40 amperes for No. 8 and 50 amperes
for No. 6 copper wire sizes. We must perform these checks and limit the OCPD
to these conditions provided that OCPD-1 is equal to or greater than the
selected OCPD using this process. We finally can select the OCPD that complies
with these conditions or we select OCPD-1 if these conditions do not apply. We
will call this OCPD, OCPD-2. Now we are ready for selecting the fourth OCPD for
the terminal temperature.
Select OCPD-3 using the Wire Size and the Terminal Temperature
The terminal temperature places a limitation on the circuit because of
section 110-14(c). This requirement was implied in the NEC for many years by
section 110-3(b) that requires that listed equipment be used according to the
listing instructions. The terminal temperature and Size of the conductor is
used to select the maximum terminal ampacity using table 310-16, and this
ampacity, that is not derated, is used to select the maximum OCPD for the
maximum terminal ampacity using section 240-6. The OCPD that equals the
terminal ampacity or the next higher OCPD is selected. We will call this OCPD,
OCPD-3.
Compare OCPD-1, OCPD-2, and OCPD-3 and find the minimum and compare this to
the Low Load OCPD.
We next compare OCPD-1, OCPD-2, and OCPD-3 and select the one that is
the minimum. We will call this our High Load OCPD. We next compare our High
Load OCPD to see if it is equal to or greater than our Low Load OCPD. If it is,
the High Load OCPD becomes our final maximum OCPD and the Low Load OCPD becomes
our minimum OCPD. If the High Load OCPD is not equal to or greater than our Low
Load OCPD we must select the next higher wire size and reselect OCPD-1, OCPD-2,
and OCPD-3, select the minimum, and compare the new High Load OCPD to the Low
Load OCPD and continue this process until the High OCPD is equal to or exceeds
the the Low Load OCPD. When this condition is satisfied the High Load OCPD
becomes the Maximum OCPD and the Low Load OCPD becomes the Minimum OCPD and the
respective conductor size for the High Load OCPD becomes the conductor size that
satisfies all the conditions placed on it by the sections of the NEC used in
this process. We must remember, of course, there are other conditions in the
NEC for the other types of loads, but, in general, this process, is the most
common and can be used most of the time.
In some extreme cases, the Minimum OCPD may exceed the
Maximum OCPD for larger wire sizes, and where the circuit is a branch-circuit
and is for multiple receptacle outlets, a very unlikely situation. |